Variable Frequency AC Resonant Test System

Variable Frequency AC Resonant Test System

HDXZ-270kVA/270kV Variable Frequency AC Resonant Test System is applied for AC dielectric test for electric equipment.
1. 10kV/300mm2 cable 3km AC withstand test,capacitance≤1.1265uF,test frequency:30-300Hz, test voltage 22kV, test time 5min;
2. 35kV/300mm2 cable 1km AC withstand test,capacitance≤0.1945uF,test frequency:30-300Hz, test voltage 52kV, test time 60min;
3. 110kV/630mm2 cable 0.2km AC withstand test,capacitance≤0.0368uF,test frequency:30-300Hz, test voltage 128kV, test time 60min;
4. 110kV/63000kVA Transformer AC withstand test,capacitance≤0.02uF,test frequency:30-300Hz, test voltage below 160kV, test time 1min;
5. GIS 110kV, Switching busbar and other substation equipment, AC withstand test,test frequency:30-300Hz, test voltage below 265kV, test time 5min

Get Help